The FCU in my apartment ceiling is dripping water onto the floor — how do I stop it?
I'm in a chiller / district-cooling apartment and there's water dripping from the ceiling right where the AC vent is, onto the floor. It's not a huge amount but it's steady when the cooling's running, and there's a damp patch spreading on the ceiling.
What's causing an FCU to leak like this, and is it something a normal handyman can fix or do I need a specialist? Worried about the ceiling.
3 answers
First thing: switch that FCU off at the thermostat to stop the drip while you sort it — standing water will keep spreading on the ceiling and can reach the light fittings.
Nine times out of ten this is a blocked condensate drain, and here's the logic: your fan-coil unit chills the air, and that pulls a surprising amount of water out of our humid air. That water is supposed to run out through a small drain line. When dust and algae block that line, the water has nowhere to go — it backs up in the drain tray and overflows through the ceiling. Exactly your symptom, and exactly why it only drips when the cooling's running.
The fix is to clear and flush the drain line and clean the tray — straightforward for the right person, and they'll usually add a slope/anti-algae treatment so it doesn't recur.
Less common causes if the drain's clear: chilled-water pipes sweating because their insulation has failed (they drip along their length, not just at the FCU), or a cracked drain pan.
This is a chilled-water / FCU job rather than a general handyman one — the FCU sits above a false ceiling and the drain and pan need doing properly. Background on why there's so much water in the first place: the condensate drain explainer.
Had exactly this — turned out to be a completely gunged-up drain line. They cleared it, flushed it and treated it, and it's been dry since. The 'turn it off first' advice is right, I let mine run and it stained the ceiling before I got someone out.
Turned it off straight away — drip stopped almost immediately, which fits the backed-up-drain explanation. Getting a chiller specialist in to flush it properly. Thanks for the quick, clear answer.
People also asked
- Our district-cooling flat: is the annual FCU service actually worth paying for, and what should it include?3 answersWater Chiller Service
- AHU vs FCU — what's the difference, and which one is in my building? Confused about what actually gets serviced.3 answersWater Chiller Service
- My chilled-water AC (FCU) isn't cooling well — could it be a valve or a clogged strainer, not the chiller?4 answersWater Chiller Service
More in Water Chiller Service
- How can I troubleshoot a water chiller that is not cooling properly?2 answersWater Chiller Service
- The chilled-water riser pipes in our building's shaft are sweating and dripping — is the insulation wrong, and whose responsibility is it?3 answersWater Chiller Service
- After a power cut our AC/chiller won't restart — is it broken, or a protection lockout, and what can I safely try?3 answersWater Chiller Service
- Downtown apartment on district cooling, the AC is weak and the bill seems high, what can we actually do?2 answersWater Chiller Service
- Pre-summer cooling checklist for a Dubai villa, getting AC and the chiller or FCU side ready before peak heat?2 answersWater Chiller Service
- Our building's water chiller is ageing and the bills are creeping up, how do we decide repair versus replace?2 answersWater Chiller Service